Viessmann Heat Pump: Install DHW temperature sensor
Install DHW temperature sensor on a Viessmann heat pump: Mount the DHW sensor on the tank so it reads true water temperature. Poor contact can let the system overheat the tank.
Applies to: DHW tank installations
How to fix install dhw temperature sensor: step by step
- Turn off power and fuel to the DHW tank.
- Remove the lower access panel below the display unit.
- Unscrew the sensor from the control board and extend the cable with field-supplied 18 AWG two-wire cable.
- Strip the sensor lead ends fully; they are left unstripped at the factory.
- Mount the sensor flat on the tank surface, vertically above or beside the bottom element, between steel tank and insulation.
- If insulation does not hold the sensor firmly, cover it with a 2 in (50 mm) square of adhesive insulation or aluminum duct tape.
- Route the cable back to the junction box and reconnect it to the control board.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 28-29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.