Viessmann Heat Pump: Hydronic connection requirements
Hydronic connection requirements on a Viessmann heat pump: Requirements for connecting the outdoor unit to the closed-loop heating system and protecting it from freezing and power loss.
Applies to: Outdoor unit AM2V 020028, 034043, 051078
Common causes of hydronic connection requirements
- Vibration transmitted into the building piping if rigid connections are used.
- Freezing of the condenser if the unit is switched off in freezing outdoor temperatures.
- Freezing of the heating circuit if power fails and no antifreeze or isolation is used.
How to fix hydronic connection requirements: step by step
- Use a closed-loop hydronic system. Minimum heating medium pressure is 8 PSI (0.5 bar).
- Follow applicable hydronic standards.
- Size the connecting pipes to the indoor unit for adequate heating medium flow (see technical data table).
- Connect the heat pump to the hydronic system with flexible piping.
- Insulate heating medium pipes and connections.
- Do not switch off the unit when outdoor air is below freezing.
- If power failure is a risk, isolate the heat pump heating circuit from the hydronic module with an additional heat exchanger and fill the heat pump heating circuit with antifreeze.
- Install a solids separator at the unit inlet. This is a prerequisite for the warranty.
- Make the hydronic layout so the indoor unit can run the heating circuit without the outdoor unit.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
0200280340430510780340043AM2V 020028AM2V 034043AM2V 051078
Source: Vitocal 100-AW AM2V Technical Data Manual, p. 31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.