Viessmann Heat Pump: Freeze stat lockout on open loop
Freeze stat lockout on open loop on a Viessmann heat pump: The freeze stat protects the liquid-to-refrigerant heat exchanger from freezing. It reads refrigerant temperature leaving the water coil in heating mode. If that temperature drops below the freeze set point, the unit locks out and must be reset manually.
Applies to: Open loop systems in heating mode
Common causes of freeze stat lockout on open loop
- Low water flow or too low water temperature from the well.
- Heat exchanger scaling or debris restricting flow.
How to fix freeze stat lockout on open loop: step by step
- Check strainer for debris and clean it.
- Confirm well flow meets 2-3 GPM per ton.
- Check water quality against the acceptable range before reset.
- Reset the freeze lockout manually once the cause is cleared.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: Vitocal 100-WA technical data manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.