Viessmann Heat Pump: DHW piping sizing to the indoor unit
DHW piping sizing to the indoor unit on a Viessmann heat pump: DHW piping must not restrict flow, so the internal pump has enough head to push water through the heat exchanger.
Applies to: Indoor unit DHW connections
How to fix dhw piping sizing to the indoor unit: step by step
- Make the DHW supply and return piping between the indoor unit DHW connections and the DHW tank at least the same size as the indoor unit outlets.
- With a non-Viessmann tank, calculate the tank coil pressure drop against the indoor unit pump residual head to confirm adequate flow.
- Be aware that undersized DHW piping can cause inadequate DHW supply.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
0200280340430510780340043AM2V 020028AM2V 034043AM2V 051078
More commissioning tips for heat pump
Source: Vitocal 100-AW AM2V Technical Data Manual, p. 31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.