Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Heat Pump: DHW desuperheater piping requirements

Updated · by Aurora Star Tech Inc.

DHW desuperheater piping requirements on a Viessmann heat pump: Use isolation valves and two drain valves so the pump can be serviced without draining the tank. Use a horizontal swing check valve to stop the tank overheating. Copper must match the unit fittings; if 1 in. (25 mm) copper is used, reduce it as close to the tank as possible. Use metal fittings within 12 in. (300 mm) of the desuperheater tee. With a Marathon plastic tank use mechanical fittings at the tank only, and never use plastic fittings between the tank and the unit. Follow the tank installation instructions.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: DHW tank with desuperheater

How to fix dhw desuperheater piping requirements: step by step

  1. Install isolation valves and two drain valves (tank draining and purging).
  2. Install a horizontal swing check valve.
  3. Use metal fittings within 12 in. (300 mm) of the desuperheater tee.
  4. Reduce 1 in. copper to match the unit as close to the tank as possible.
  5. Upsize long pipe runs if pressure drop is too high.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Heat Pump codes

Models

AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056

More commissioning tips for heat pump

Source: Vitocal 100-WA technical data manual, p. 10. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service