Viessmann Heat Pump: Current loop (S line) communication fault, no code shown

Updated · by Aurora Star Tech Inc.

Current loop (S line) communication fault, no code shown on a Viessmann heat pump: Diagnosis of the S current loop between indoor and outdoor units. Normal reading: DC voltage between N/L2 and S alternates between positive and negative. A reading fixed near 0 or always positive points to a fault.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocal IND-A DLFUAA air handler, models 18XAK to 60XAK

Common causes of current loop (s line) communication fault, no code shown

  • Wiring fault between indoor and outdoor units
  • Wiring fault between terminals and PCBs
  • Short circuit in a high-voltage component (4-way valve, heater, fan)
  • Short circuit in the electronic expansion valve coil
  • Faulty IPM board, main PCB, indoor PCB or outdoor PCB

How to fix current loop (s line) communication fault, no code shown: step by step

  1. Power off, then restart the unit 2 minutes later and check whether the error disappears.
  2. Measure DC voltage between N/L2 and S: black probe to S, red probe to N/L2.
  3. If the value is fixed near 0 or always positive, check the wiring between indoor and outdoor units.
  4. Check the wiring from the outdoor terminal to the outdoor PCB and between PCBs.
  5. Check the wiring from the indoor terminal to the indoor PCB.
  6. Check whether the power LED is on.
  7. Unplug each high-voltage component on the main PCB (4-way valve, heater, AC fan) and check its resistance for a short.
  8. Replace any short-circuited component and the main PCB.
  9. Unplug the electronic expansion valve and check the DC 5 V and 12 V supply to the main PCB.
  10. Check the AC voltage at L and N output to the IPM board; it should match the power input.
  11. Check the DC 5 V and 12 V from the IPM board to the main PCB.
  12. Replace the IPM board, the main PCB, the EEV coil, or the indoor or outdoor PCB as the checks indicate.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Heat Pump codes

Source: Viessmann Vitocal IND-A DLFUAA service manual, p. 18-19. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.