Viessmann Heat Pump: Connect a stand-alone indirect DHW tank
Connect a stand-alone indirect DHW tank on a Viessmann heat pump: A DHW temperature sensor is required when a stand-alone DHW tank is used. The sensor is supplied with the heat pump; other fittings are field supplied.
Applies to: DHW connections, indoor unit
How to fix connect a stand-alone indirect dhw tank: step by step
- Locate the DHW temperature sensor well on the Vitocell tank and install the sensor using the tank instructions.
- Size the indirect DHW tank from the building's forecast DHW use.
- If a non-Viessmann tank is used, verify the Viessmann DHW sensor works correctly with that tank manufacturer.
- Install a temperature tempering valve in the DHW supply line (strongly recommended by Viessmann for non-Viessmann tanks).
- If no DHW tank is connected, cap the DHW tank port and set the indoor unit to operate without a DHW tank in the Service/Configuration Menu (DHW Tank setting, p. 62).
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Source: Viessmann Vitocal 100-AW AM2V installation manual, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.