Viessmann Heat Pump: Communication line and reactor checks (remarks)
Communication line and reactor checks (remarks) on a Viessmann heat pump: Test notes for the communication signal and the reactor used with EL01 diagnosis.
Applies to: DLFSHC outdoor unit, EL01 diagnosis
Common causes of communication line and reactor checks (remarks)
- Reactor shorted to ground
- Reactor open or shorted
How to fix communication line and reactor checks (remarks): step by step
- Use a multimeter to measure DC voltage between the 2 port (or S or L2) and the 3 port (or N or S). Red probe on the 2 port (or S or L2), black on the 3 port (or N or S).
- A running unit shows a voltage that alternates between positive and negative values.
- If the outdoor unit is faulty, the voltage stays in a narrow positive range.
- If the indoor unit is faulty, the voltage stays fixed.
- Measure the reactor resistance with the reactor disconnected from the capacitor. Normal is about zero ohms. If not, the reactor is faulty. Check that it is not shorted to ground.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Source: Viessmann Vitocal IND-H DLFSHC service manual, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.