Viessmann Heat Pump: Closed loop water quality and antifreeze requirements
Closed loop water quality and antifreeze requirements on a Viessmann heat pump: Requirements for fill and top-up water and for antifreeze in closed loop ground systems.
Applies to: Vitocal 100-WA closed loop systems
Common causes of closed loop water quality and antifreeze requirements
- Antifreeze below the minimum level lets the system freeze and damage the unit, and this is not covered by warranty.
- Sulphur in feed water, high hardness or wrong pH can cause build-up and problems.
How to fix closed loop water quality and antifreeze requirements: step by step
- Keep at least 25% propylene glycol in the unit and ground loop at all times.
- Do not exceed 35% antifreeze. Above 35% reduces performance, so account for it in equipment selection.
- Use only antifreeze made for water source heat pumps. Do not use automotive silicate based antifreeze.
- Check that feed water has no sulphur and that pH is between 7 and 9 after some run time. Treat the water if it is not.
- Keep total hardness of fill and top-up water below 350 ppm. Treat hard water where needed.
- Check for a backflow preventer in the automatic feed when using antifreeze.
- Check that expansion tanks, radiation and other components are compatible with the glycol mix.
- Check the total system often when it is filled with antifreeze.
- Tell the owner the system contains a glycol mix and give them the antifreeze Safety Data Sheet.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: Vitocal 100-WA installation, service and operating instructions, p. 75. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.