Viessmann Heat Pump: Closed loop (ground loop) piping and antifreeze
Closed loop (ground loop) piping and antifreeze on a Viessmann heat pump: Ground loops must always hold a minimum of 25% propylene glycol. Failure freezes the system and damages the unit, and that damage is not covered by warranty.
Applies to: Vitocal 100-WA closed loop systems
Common causes of closed loop (ground loop) piping and antifreeze
- Antifreeze below 25% propylene glycol, causing freeze damage
- Insufficient loop velocity leaving air or debris in branches
How to fix closed loop (ground loop) piping and antifreeze: step by step
- Do not use PVC or CPVC piping on any ground loop connection; PVC or CPVC may only be used for condensate lines.
- Size the loop pump to the project-specific loop design; residential systems typically need one pump per unit.
- Provide suitable access for purging the outside loop and isolation valves for purging the inside plumbing.
- Purge the loop so every branch reaches a minimum velocity of 2 feet per second.
- Use the purge ports for anti-freeze charging.
- Keep a minimum of 25% propylene glycol in the unit and ground loop at all times.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: Vitocal 100-WA installation, service and operating instructions, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.