Viessmann Heat Pump: Closed loop flow and loop temperature
Closed loop flow and loop temperature on a Viessmann heat pump: Closed loops need a minimum of 3 GPM/ton (11.5 LPM/3.5 kW), based on a loop designed for 32 to 90°F (0 to 32°C). Use higher flow if design temperatures fall outside that range. The loop pump depends on the project loop design; residential systems typically use one pump per unit.
Applies to: Closed loop systems
How to fix closed loop flow and loop temperature: step by step
- Confirm loop design temperature is within 32-90°F.
- Size the loop pump for at least 3 GPM/ton.
- Increase flow if loop temperatures fall outside the range.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
More commissioning tips for heat pump
Source: Vitocal 100-WA technical data manual, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.