Viessmann Heat Pump: Auto Changeover wiring and thermostat setup

Updated · by Aurora Star Tech Inc.

Auto Changeover wiring and thermostat setup on a Viessmann heat pump: With Auto Changeover, the thermostat sets heating or cooling mode through the changeover relay on FN2; the indoor unit dial only turns the system on or to standby.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocal 100-AW AM2V indoor unit with Auto Changeover

How to fix auto changeover wiring and thermostat setup: step by step

  1. Wire the field-supplied thermostat to the changeover relay on FN2.
  2. On the thermostat, select heat pump mode.
  3. Set the thermostat O/B setting to cooling.
  4. Keep the FN1 contact closed for normal operation; opening it blocks operation.
  5. Check the relay light: OFF means heating mode, ON means cooling mode.
  6. Check thermostat OFF behaviour, since it varies by thermostat (some default to heating, others keep the last mode).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Heat Pump codes

Source: Vitocal 100-AW AM2V installation manual, p. 30. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.