Configure BACnet/IP settings on the gateway on a Viessmann general: Set up the gateway over a direct connection to a computer before joining it to the BMS network.
Applies to: Versatronik 535 Solar gateway, BACnet IP
How to fix configure bacnet/ip settings on the gateway: step by step
- Connect your computer directly to the gateway's BACnet interface with no other devices on the link (isolated network).
- Set the computer to automatic IP (DHCP), or set its IP address to 192.168.88.90 with subnet mask 255.255.255.0.
- Restart the gateway by cycling power off and on.
- Open a browser and go to http://192.168.88.89/admin.
- Log in with the default user name and password 'admin' (change it on the Change Password screen).
- Open the Configuration pages and set the BACnet Device Settings, pressing SAVE on each screen you change.
- Confirm the Activate Configuration screen and choose SAVE to store settings; the gateway reboots automatically.
- Once rebooted, join the gateway to the network without duplicating an IP address already in use, then access the configuration pages via 192.168.88.89 or the newly assigned address.
Source: Versatronik 535 Solar BACnet IP manual, p. 12, 13. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.