Viessmann Boiler: Wiring boiler return mixing or isolation/modulating valve actuator

Updated · by Aurora Star Tech Inc.

Wiring boiler return mixing or isolation/modulating valve actuator on a Viessmann boiler: Install the 120V or 24V valve adaptor and connect the valve actuator through it.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 100 GC1 valve actuator wiring

How to fix wiring boiler return mixing or isolation/modulating valve actuator: step by step

  1. Disconnect power to the control.
  2. Mount the 120V or 24V valve adaptor on the DIN rail inside the connection enclosure.
  3. Insert the plug gS into socket gS on the control.
  4. Fasten the cable with a tie (see page 30).
  5. Connect the black wire of the adaptor to terminal aBH on the DIN rail (terminal 8, 9 or 10).
  6. Connect valve actuator wires to the adaptor terminals as shown in the figures.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitotronic 100, type GC1

Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 37. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.