Viessmann Boiler: Wire the push-in DIN terminals in the junction box
Wire the push-in DIN terminals in the junction box on a Viessmann boiler: The L, N, G terminals use push-in clamps. Wire sizes are limited.
Applies to: Vitotronic 300 GW6B junction box DIN terminals
How to fix wire the push-in din terminals in the junction box: step by step
- Push in the orange button on the terminal before inserting or removing a wire.
- Use solid, stranded or ferrule-terminated wire.
- Use wire between 26 AWG (minimum) and 12 AWG (maximum).
- Use a ferrule on stranded wire to prevent fraying.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 GW6B installation and service manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.