Viessmann Boiler: Wire space heating pump output to zone controller (outdoor reset with Como OT)
Wire space heating pump output to zone controller (outdoor reset with Como OT) on a Viessmann boiler: For a Vitodens 100-W (WB1A/B) with Versatronik Como OT for outdoor reset and no room thermostat. The 120 VAC space heating pump output feeds the zone controller. When the output is on, the zone controller sees the signal and any zone with a call will run its pump or valve. With no signal, no zone starts on a thermostat call.
Applies to: Versatronik 10.WB1 with Versatronik Como OT outdoor reset
How to fix wire space heating pump output to zone controller (outdoor reset with como ot): step by step
- Disconnect power to the Versatronik 10.WB1 and the zone controller.
- Remove the ZC/ZR jumper from the zone controller.
- Connect the L output of the Versatronik space heating pump output to the ZC terminal of the zone controller.
- Power both devices and test operation.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 10.WB1 installation and operating manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.