Viessmann Boiler: Wire pumps drawing more than 2FLA
Wire pumps drawing more than 2FLA on a Viessmann boiler: Pumps above the direct output rating must be switched through a contactor.
Applies to: 120V pumps with amperage draw above 2FLA
How to fix wire pumps drawing more than 2fla: step by step
- Install a field-supplied contactor or relay rated 120VAC 1A on the DIN rail in the junction box.
- Connect the contactor to the 120V output and power the pump from the field power supply with disconnect and protection.
- Connect the pump to the contactor output.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 GW6B installation and service manual, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.