Viessmann Boiler: Wire one combustion air device to several boilers through the common interface
Wire one combustion air device to several boilers through the common interface on a Viessmann boiler: A single combustion air device on a multiple boiler system needs a Common Combustion Air Interface. Each boiler gets its own adaptor.
Applies to: Multiple boiler systems with a shared combustion air device
How to fix wire one combustion air device to several boilers through the common interface: step by step
- Install a Combustion Air Device Adaptor on each boiler (part 7134 563).
- Install the Common Combustion Air Device Interface (part 7134 604) as its manual says.
- Wire the interconnecting cable between the interface and each boiler adaptor. Use field-supplied wire.
- Use AWG 14 wire, rated 120 VAC, max 5 FLA.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitocontrol-S VD2/CT3/CM2
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Vitotronic 100 GC1
Source: Vitotronic 100 GC1 / Vitocontrol-S installation manual, p. 57. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.