Viessmann Boiler: Wire DHW, pool or spa demand to zone controller
Wire DHW, pool or spa demand to zone controller on a Viessmann boiler: For multiple DHW, pool or spa demands, or an elevated boiler water temperature demand. The boiler pump connects to the Vitodens pump module, which sends a signal to the Versatronik. When the DHW aquastat or set-point control calls, its dry contact closes the DHW AQ input, which starts the DHW pump output and calls the zone controller.
Applies to: Versatronik 10.WB1 DHW, pool or spa pump control
How to fix wire dhw, pool or spa demand to zone controller: step by step
- Remove power from the Versatronik 10.WB1 and the zone control.
- Remove the ZC/ZR jumper from the zone controller.
- Connect the L output of the Versatronik DHW heating pump output to the ZC terminal of the zone controller.
- Connect the potential-free (dry contact) output of the zone controller to the Versatronik DHW AQ input terminals.
- Power both devices and test operation.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 10.WB1 installation and operating manual, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.