Viessmann Boiler: Water side piping with Vitotronic control
Water side piping with Vitotronic control on a Viessmann boiler: Use a spring-loaded flow-check valve in heating circuits without mixing valves, to prevent gravity circulation of heat into the system in summer. Flush the system before connecting.
Applies to: Vitorond 100 VR1 with Vitotronic control
Common causes of water side piping with vitotronic control
- Sludge left in an older system settling in the boiler
How to fix water side piping with vitotronic control: step by step
- Flush the heating system thoroughly, especially older systems.
- Install a spring-loaded flow-check valve in circuits without mixing valves.
- Remove the top back panel before connecting pipe fittings.
- Connect the system supply to the supply connection with NPT fittings.
- Connect the system return to the return connection with NPT fittings, using the return injector.
- Install the gauge with brass extension coupling in the 1/2 in opening.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 VR1 installation and service instructions, p. 22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.