Viessmann Boiler: Vertical vent termination location and roof passage

Updated · by Aurora Star Tech Inc.

Vertical vent termination location and roof passage on a Viessmann boiler: Vent termination must be kept out of reach of snow and must not be blocked by drifting snow. Special positive pressure vent systems through a roof need extra height. Other appliance flues must not share the vent.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: All vertical and roof vent installations

How to fix vertical vent termination location and roof passage: step by step

  1. Place the vent termination at least 12 in. (305 mm) above the anticipated snow level and where snow cannot block it.
  2. On a roof pass-through with special positive pressure venting, extend the vent at least 18 in. (450 mm) above the highest roof penetration point and any obstruction within 18 in. (450 mm) horizontally.
  3. Do not route the special vent into, through or within any other vent such as an existing masonry or factory-built chimney.
  4. Use a masonry chimney flue only if no other appliance is vented into it.
  5. On a flat roof, install the vent in line with local regulations, CAN/CSA-B149.1 or .2, or ANSI Z223.1 / NFPA 54.
  6. Support the venting system with supports rated for the weight and design of the materials, using anchor plates, wall supports, roof supports, floor supports or hangers. Brace it as needed with wall bands, guy wire bands or roof braces. The boiler does not carry the vent weight.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0

Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 57. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.