Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Verify gas input by clocking the gas meter

Updated · by Aurora Star Tech Inc.

Verify gas input by clocking the gas meter on a Viessmann boiler: Time how long the boiler takes to burn a set amount of gas and compare with the nameplate input. Other gas appliances on the meter must be off during the test.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 300 CU3A 26 to 199 (low altitude)

How to fix verify gas input by clocking the gas meter: step by step

  1. Turn off all other gas appliances served by the meter.
  2. Time how many seconds the boiler takes to use 10 ft3 of gas.
  3. Confirm the heating value of the gas with the gas utility first.
  4. Calculate input: (3600 x 10) divided by seconds gives ft3 per hour; multiply by heating value (Btu/ft3) to get Btu/h.
  5. Example: a 199 model at 181 seconds per 10 ft3 with 1000 Btu/ft3 gives about 199,000 Btu/h, which is correct.
  6. An input 5% under the rating is acceptable. Do not overfire the boiler.
  7. Metric or low altitude formulas: INPUT = (3600 / t) x 1000 with t in seconds per 1 ft3; or INPUT = (3600 x 0.01 x 1000 x 35.31) / T with T in seconds per 0.01 m3 of natural gas. These apply to low altitude only.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 27. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977