Viessmann Boiler: Venting connection and vent routing
Venting connection and vent routing on a Viessmann boiler: Vent pipe routing and piping support rules for the boiler venting connection.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352
How to fix venting connection and vent routing: step by step
- Use the vent pipe adaptor that comes pre-installed on the boiler.
- Run single-wall or coaxial venting through the side wall or roof by the shortest route.
- Keep a rising slope of at least 3 degrees toward the terminal.
- Support the piping with a proper suspension method. Piping must not rest on or be supported by the boiler.
- Use a moderate amount of pipe dope.
- If using single-wall venting (room-air dependent), remove the outer gasket before installation.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Installation Instructions, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.