Viessmann Boiler: Vent pipe installation
Vent pipe installation on a Viessmann boiler: Use approved vent material only. Keep the run short with few elbows. Support horizontal runs so they do not sag, and keep them as short as possible.
Applies to: Vitorond 100 VR1 oil-fired boilers
How to fix vent pipe installation: step by step
- Route the vent for the shortest path with minimum elbows.
- Fit the factory vent adaptor to the flue gas collar with three equally spaced corrosion-resistant self-tapping screws and high-temperature silicone, or equivalent.
- Connect the chimney through an 18 in (457 mm) field-supplied, slightly inclined intermediate section.
- Pitch horizontal runs up at least 1/4 in per ft from the boiler to the terminal.
- Support horizontal runs with metal strap every 4 ft (1.2 m).
- Seal all flue joints.
- Insulate any uninsulated vent pipe to reduce flue gas cooling and noise.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 VR1 installation and service instructions, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.