Update LON participant list (Vitotronic 300-K cascade) on a Viessmann boiler: Run this after all communication connections are made. The Vitotronic 300-K must be the error manager (its default), and each gateway needs a unique LON participant number.
Applies to: Vitotronic 300-K cascade control with Versatronik 501 gateways
How to fix update lon participant list (vitotronic 300-k cascade): step by step
- Confirm the Vitotronic 300-K is coded as the error manager (default). See the 300-K manual at address 79:01.
- Set a unique LON participant number on each gateway with its rotary dial. Check for duplicates.
- Press OK and the Menu button together to open the Service menu, then press OK.
- Arrow down to Service Functions and press OK.
- In Service Functions, make sure Participant Check is highlighted. Arrow up or down to highlight it if needed, then press OK.
- Arrow down to Delete List? and press OK.
- Wait for all devices to report back. Re-entering Participant Check too early shows No Participant, so wait and then enter Participant Check again.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Versatronik 501 and 501D LON gateway manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.