Viessmann Boiler: Underfloor heating overheat protection
Underfloor heating overheat protection on a Viessmann boiler: For underfloor heating, an extra immersion or strap-on aquastat must be installed in the low temperature underfloor loop, downstream of the mixing valve, to shut off the pump and/or boiler. High water temperatures can damage concrete slabs.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
How to fix underfloor heating overheat protection: step by step
- Install an immersion or strap-on aquastat in the low temperature underfloor loop, downstream of the mixing valve.
- Wire the aquastat to de-energize the pump and/or boiler on high temperature.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
More commissioning tips for boiler
Source: Vitodens 200-W B2HB installation manual, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.