Viessmann Boiler: Thermostat, off-peak and secondary pump wiring

Updated · by Aurora Star Tech Inc.

Thermostat, off-peak and secondary pump wiring on a Viessmann boiler: Call-for-heat and off-peak inputs use voltage-free contacts. A secondary pump can be run from Pump 2.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotron 100 VLN2 controls

How to fix thermostat, off-peak and secondary pump wiring: step by step

  1. Use voltage-free (dry contact) switches from a thermostat, valve end switches or zone panel.
  2. Run 2 x 18 gauge wire from the thermostat to the TT terminals.
  3. Keep the thermostat away from other heat sources.
  4. For off-peak control, connect a voltage-free contact to OP. Keep the blue/white jumper in place if it is not used.
  5. Connect an optional secondary pump to Pump 2. It starts when the thermostat contacts close.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

VLN2 04VLN2 06VLN2 08VLN2 12VLN2 14.4

Source: Vitotron 100 VLN2 installation and service instructions, p. 11. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.