Updated · by Aurora Star Tech Inc.

Test the flow switch on a Viessmann boiler: The B2HA series has a flow sensing device. Low flow opens the switch, the burner shuts down and it will not restart until adequate flow returns.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA 19, 28, 35

Common causes of test the flow switch

  • Flow below the safe operating set point of the boiler

How to fix test the flow switch: step by step

  1. Throttle the water flow to or from the boiler.
  2. Confirm the boiler shuts down once flow drops below its safe operating set point.
  3. Restore full flow and confirm the burner restarts only after adequate flow is back.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitodens 200-W B2HA service instructions, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.