Viessmann Boiler: Test fixed high limit (simulation #2, valve closed)
Test fixed high limit (simulation #2, valve closed) on a Viessmann boiler: Alternate high limit test that uses a closed boiler valve and a jumpered flow switch.
Applies to: Vitodens 200-W B2HA 45, 60
How to fix test fixed high limit (simulation #2, valve closed): step by step
- Close the boiler valve and jumper across the flow switch.
- Run the boiler at high fire. The control should shut it down through the coding card (on B2TB models, set coding address 06 to maximum).
- Keep the boiler temperature rising until the fixed high limit trips.
- After the limit trips, slowly open the boiler valve to cool the boiler down.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.