Viessmann Boiler: Test fixed high limit (simulation #1, pump unplugged)

Updated · by Aurora Star Tech Inc.

Test fixed high limit (simulation #1, pump unplugged) on a Viessmann boiler: Field test of the manual reset high limit. Only do this where required by law, and the manufacturer is not responsible for damage from overheating during this test.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA 45, 60. On boilers 19 to 100 with flow switches, jumpering the flow switches may be needed during testing.

How to fix test fixed high limit (simulation #1, pump unplugged): step by step

  1. Make sure the boiler and boiler pump are in normal condition. Pump output sÖ is the boiler pump.
  2. Remove the cover from the back of the boiler control to reach the control plugs.
  3. In the extended menu, select Test mode, then flue gas test ON, and press OK.
  4. Wait for the burner to fire and go to high fire.
  5. When the burner lights, gently unplug boiler pump plug sÖ from the control board using pliers.
  6. Watch the boiler temperature on the display. It rises, then the burner shuts off.
  7. The temperature should keep rising to 210°F (99°C) and the high limit should trip with an F2 fault.
  8. If the limit is not reached, repeat the test. Two minutes after the burner shuts off, plug the pump in for a maximum of 1 second.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.