Viessmann Boiler: System version 7: Vitocrossal 300 lead boiler with Vitorond 200 lag boiler and shunt pump return control
System version 7: Vitocrossal 300 lead boiler with Vitorond 200 lag boiler and shunt pump return control on a Viessmann boiler: Vitocrossal 300 (CT3) is the lead boiler and Vitorond 200 (VD2) is the lag boiler, run by a Viessmann outdoor-reset cascade control with modulating boiler water temperature. The CT3 has two return connections: circuits with the higher return temperature go to the upper connection, lower-temperature circuits go to the lower connection, and at least 15% of rated output must be on the lower connection. Return temperature control on the Vitorond uses the shunt pump and an isolation valve. Sensor T1 controls the isolation valve and sensor T2 switches the shunt pump. The LON-BUS sets the boiler supply temperature from the highest mixing-circuit demand plus an adjustable differential.
Applies to: System version 7 (lead Vitocrossal 300 CT3, lag Vitorond 200 VD2)
How to fix system version 7: vitocrossal 300 lead boiler with vitorond 200 lag boiler and shunt pump return control: step by step
- Connect at least 15% of rated output to the lower return connection on the Vitocrossal 300.
- Place sensor T1 to control the isolation valve and sensor T2 to switch the shunt pump, as shown in the system diagram.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitocontrol-S VD2/CT3/CM2
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Vitotronic 100 GC1
Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.