Viessmann Boiler: System version 7 design: three-way mixing valve with several heating circuits
System version 7 design: three-way mixing valve with several heating circuits on a Viessmann boiler: Lead boiler is a Vitocrossal 300 with lag Vitorond 200 boilers, run by an outdoor-reset control with modulating boiler water temperature and load-based sequencing. Heating circuits with higher return temperature go to the upper return connection, lower ones to the lower return connection. At least 15% of rated output must go to the lower return connection. Sensor T1 reads the return temperature and the boiler control holds the mixing valve so the return never drops below minimum. Boiler supply temperature follows the highest mixing circuit demand plus an adjustable differential. Intended for heating circuits with temperature differentials of 20 °C / 68 °F or more.
Applies to: System version 7
How to fix system version 7 design: three-way mixing valve with several heating circuits: step by step
- Connect at least 15% of rated output to the lower return connection.
- Connect the T1 return sensor so it reads the return temperature.
- Verify the connection diagram on site for completeness and function, since it is only a recommendation.
- Use field-supplied motor contactors or starters for single-phase and three-phase pumps.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 24-26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.