Viessmann Boiler: System version 6: heating circuit, low temperature circuit and Vitorond with shunt pump
System version 6: heating circuit, low temperature circuit and Vitorond with shunt pump on a Viessmann boiler: Vitocrossal 300 as lead boiler and Vitorond 200 as lag boiler, controlled by a Viessmann control system with outdoor reset, modulating boiler water temperature and load-dependent sequential control. Return temperature control for the Vitorond uses the shunt pump and a closing isolation valve. Sensor T1 controls the isolation valve and sensor T2 switches the shunt pump. The return temperature control is either an accessory or must be provided on site.
Applies to: System version 6, Vitocrossal 300 with Vitorond 200 (125 kW to 500 kW)
How to fix system version 6: heating circuit, low temperature circuit and vitorond with shunt pump: step by step
- Connect at least 15% of the rated output to the lower return connection.
- Set T1 and T2 coding only on the low temperature boiler as marked in the coding table.
- Set the Vitocrossal 300 as permanent lead boiler using code 39 (value 1 to 4).
- Check the connection diagram on site for completeness and function, because it is only a recommendation.
- Wire single-phase and three-phase pumps through field-supplied motor contactors or starters.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 21-23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.