Viessmann Boiler: System version 4: return temperature control with low loss header and three-way mixing valve
System version 4: return temperature control with low loss header and three-way mixing valve on a Viessmann boiler: Vitorond 200 boiler with Vitotronic 100 GC1 on each boiler and one Vitotronic 300-K MW1S. The return temperature is controlled with a three-way mixing valve and a low loss header. Sensor T1 closes the mixing valve in proportion when the minimum return temperature is not reached, which protects the boiler. The sensor in the low loss header controls the supply temperature. Suited to older systems, systems where the hydraulics are not clearly defined, and systems where downstream heating circuits cannot be controlled.
Applies to: System version 4, Vorond 200 with Vitotronic 100 GC1 and Vitotronic 300-K MW1S
How to fix system version 4: return temperature control with low loss header and three-way mixing valve: step by step
- Code every Vitotronic 100 GC1 as shown in the system version 4 coding table.
- Size each boiler circuit pump so its flow is at least the maximum total heating circuit flow; recommended 110%.
- Check the connection diagram on site for completeness and function, because it is only a recommendation.
- Wire single-phase and three-phase pumps through field-supplied motor contactors or starters.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 16-17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.