Viessmann Boiler: System version 3: common supply pump and low pressure manifold
System version 3: common supply pump and low pressure manifold on a Viessmann boiler: Used when the distribution manifold is in a remote location (more than 20 m / 65 ft). T1 reduces or closes the mixing valves when the minimum return temperature is not reached. The common supply pump should be sized to 110% of the total heating system flow rate.
Applies to: Vitorond 200 VD2, system version 3
How to fix system version 3: common supply pump and low pressure manifold: step by step
- Size the common supply pump to 110% of total system flow.
- Set coding 0D: 1 and 4C: 2 for the wiring diagram where heating circuit control units are not connected via LON BUS.
- Connect the contactor relay and downstream control unit so that the switch closes to signal close mixing valves.
- Set coding 4d: 0 for the common supply pump on plug sL.
- Check the connection diagram on site before commissioning.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitocontrol-S VD2/CT3/CM2
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Vitotronic 100 GC1
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 13-14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.