Updated · by Aurora Star Tech Inc.

System version 2: shunt pump for return temperature control on a Viessmann boiler: Used where the distribution manifold is close to the boiler. The boiler water flow is reduced by the motorized isolation valve. T2 switches on the shunt pump when the minimum return temperature is not reached. If that is not enough, T1 must cut boiler water flow by at least 50% through the isolation valve or the heating circuit control units. If T1 cannot act on the isolation valves, it must regulate the downstream mixing valves instead.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitorond 200 VD2, system version 2

How to fix system version 2: shunt pump for return temperature control: step by step

  1. Size the shunt pump to about 30% of the total boiler throughput.
  2. Connect T2 to plug aJB and T1 to plug aJA, then set codings 4A and 4b to 1.
  3. Confirm the minimum return temperature is reached. If not, reduce boiler flow by at least 50% using T1.
  4. Set up the Vitocontrol-S coding per the table for system version 2.
  5. Verify the connection diagram on site, since it is a recommendation only.
  6. Use field-supplied motor contactors or starters for single-phase and three-phase pumps.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitocontrol-S VD2/CT3/CM2

300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1

Vitotronic 100 GC1

Vitotronic 100, type GC1

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 11. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977