Viessmann Boiler: System layout 8: DHW tank, low-loss header and three zone circuits
System layout 8: DHW tank, low-loss header and three zone circuits on a Viessmann boiler: Layout for Vitodens 200-W B2HA/B2HB with a DHW storage tank, a low-loss header and three zone circuits. A low-loss header is strongly recommended and is sold as an accessory.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
How to fix system layout 8: dhw tank, low-loss header and three zone circuits: step by step
- Wire the boiler pump to output 20 and the DHW pump to output 21.
- Wire zone circuit 1 to output 157 on the boiler.
- Wire zone circuits 2 and 3 to outputs A1 and A2 on the AM1 extension module (accessory).
- Connect the thermostats for zone circuits 1, 2 and 3 as dry contacts.
- Connect the outdoor sensor, DHW sensor and supply temperature sensor as shown in the layout.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
More commissioning tips for boiler
Source: Vitodens 200-W B2HB installation instructions, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.