Viessmann Boiler: System layout 4: radiator and underfloor circuits with DHW
System layout 4: radiator and underfloor circuits with DHW on a Viessmann boiler: One direct radiator circuit and one underfloor circuit with a mixing valve, plus DHW storage. Radiator circuit flow must be at least 30% greater than underfloor flow, and total flow must be under boiler maximum.
Applies to: Mixed radiator and underfloor heating with DHW
How to fix system layout 4: radiator and underfloor circuits with dhw: step by step
- Confirm radiator circuit flow is at least 30% greater than underfloor circuit flow.
- Confirm total flow of both circuits is under boiler maximum.
- Install the mixing valve accessory kit and its temperature sensor on the underfloor circuit.
- Use a low-loss header if flow exceeds the limit on p. 30 or flow is unknown.
- Pipe the DHW circulating pump into the boiler.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HA installation manual, p. 36. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.