Viessmann Boiler: System layout 4: radiator and underfloor circuits together
System layout 4: radiator and underfloor circuits together on a Viessmann boiler: Combines a direct radiator circuit with an underfloor circuit that uses a mixing valve. The radiator circuit flow must be at least 30% higher than the underfloor circuit flow.
Applies to: Vitodens 222-F B2TB, mixed radiator and underfloor circuits
How to fix system layout 4: radiator and underfloor circuits together: step by step
- Verify the radiator circuit flow is at least 30% greater than the underfloor circuit flow.
- Verify the combined flow of both circuits is below the boiler maximum flow rate on page 30; otherwise use a low-loss header.
- Install the accessory kit for the mixing valve and the mixing valve temperature sensor.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125
Source: Vitodens 222-F, B2TB installation instructions, p. 35. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.