Viessmann Boiler: System layout 4: direct radiator circuit plus system-separated underfloor circuit
System layout 4: direct radiator circuit plus system-separated underfloor circuit on a Viessmann boiler: Radiator circuit fed by the boiler pump 20 and an underfloor circuit isolated by a plate heat exchanger with a 3-way mixing valve.
Applies to: Vitocrossal 300 CU3A, system layout 4
How to fix system layout 4: direct radiator circuit plus system-separated underfloor circuit: step by step
- Install the plate heat exchanger for system separation.
- Confirm the plate heat exchanger secondary pressure drop is less than or equal to the 3-way mixing valve pressure drop.
- Install the accessory kit for the mixing valve circuit and connect the mixing valve temperature sensor.
- Connect the boiler pump 20 to supply the radiator circuit and the plate heat exchanger.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
2635455794125160199CU3ACU3A 26CU3A 35CU3A 45CU3A 57CU3A 94CU3A 125CU3A 160CU3A 199Vitocrossal 300, type CT3
Source: Viessmann Vitocrossal 300 CU3A installation manual, p. 47. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.