Viessmann Boiler: System Example 01: cascade control for modulating boilers
System Example 01: cascade control for modulating boilers on a Viessmann boiler: Cascade controller for modulating OT boilers 1 to 8. The boiler set point comes from the heating system manager and the boiler modulates to reach it. Outdoor reset with outdoor sensor and common supply sensor. No low loss header or hydraulic separator, though closely spaced tees are possible. No DHW production, no DHW recirculation pump and no space heating control. Individual boiler pumps are run from the boiler pump output.
Applies to: Cascade of modulating OT boilers, no DHW
How to fix system example 01: cascade control for modulating boilers: step by step
- Wire outdoor sensor to terminal 1 and common supply sensor to terminal 2.
- Connect the CAN BUS H, L, -, + terminals to the Coco OT modules.
- Set the system selection to 01 during start-up.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 200 installation and operating manual, p. 21-22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.