Viessmann Boiler: Supply/return bypass for large water content systems
Supply/return bypass for large water content systems on a Viessmann boiler: Systems with volume above about 1 US gal per 13,000 Btu/h of boiler input (for example older gravity systems with large free-standing radiators) need a bypass from supply to return to prevent flue gas condensation in the heat exchanger and vent. Viessmann strongly recommends a bypass on all cast iron boilers.
Applies to: Vitorond 100 boilers on large water content systems
How to fix supply/return bypass for large water content systems: step by step
- Check the system water volume against the boiler input.
- If the system is large, install a bypass pipe from the supply pipe to the return pipe.
- Install a bypass on any system as a preventive measure, as Viessmann recommends for all cast iron boilers.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Viessmann Vitorond 100 installation and service manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.