Viessmann Boiler: Size DHW supply and return piping correctly
Size DHW supply and return piping correctly on a Viessmann boiler: DHW piping between the boiler and a Viessmann DHW tank must be at least 1-1/4 in nominal diameter. Undersized piping can cause short-cycling and poor DHW supply. Non-Viessmann tanks need coil pressure-drop calculations against pump head.
Applies to: DHW storage tank piping
How to fix size dhw supply and return piping correctly: step by step
- Use at least 1-1/4 in nominal pipe between boiler DHW connections and the DHW tank connections.
- For non-Viessmann DHW tanks, calculate the tank coil pressure drop against the boiler pump head.
- Confirm enough water flow to the boiler heat exchanger.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 100-W B1HE/B1KE Combi Installation and Service Instructions, p. 34. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.