Viessmann Boiler: Size combustion air openings
Size combustion air openings on a Viessmann boiler: Sizes are based on the total input of all oil-fired appliances in the space. Louvers and screens reduce free area, so allow for them.
Applies to: VR1 22 to 33, 91 to 140
How to fix size combustion air openings: step by step
- Unconfined space: provide 1 sq in per 5,000 Btu/h (4.5 sq cm per kWh) of total input, or use outdoor or freely communicating air.
- Confined space using indoor air: two permanent openings, one near the top and one near the bottom, each 1 sq in per 1,000 Btu/h (19.5 sq cm per kWh).
- Confined space using outdoor air, vertical duct: 1 sq in per 4,000 Btu/h (5.5 sq cm per kWh) per duct.
- Confined space using outdoor air, horizontal duct under 50 ft (15 m) equivalent length: 1 sq in per 2,000 Btu/h (11 sq cm per kWh).
- Confined space using outdoor air, direct openings to outside: 1 sq in per 4,000 Btu/h (5.5 sq cm per kWh).
- Allow for louver free area: wood louvers 20 to 25 percent, metal louvers and grilles 60 to 75 percent, unless the manufacturer states the free area.
- Use screens no smaller than 1/4 in (6 mm) mesh and keep them accessible for cleaning.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 installation and service manual, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.