Viessmann Boiler: Simplified leak test of coaxial vent (sealed combustion)

Updated · by Aurora Star Tech Inc.

Simplified leak test of coaxial vent (sealed combustion) on a Viessmann boiler: Applies only to sealed combustion with coaxial venting. Not applicable to single-wall venting.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 100-W, WB1B, coaxial vent

Common causes of simplified leak test of coaxial vent (sealed combustion)

  • Leak in the coaxial vent system

How to fix simplified leak test of coaxial vent (sealed combustion): step by step

  1. Measure the CO2 concentration of the combustion air in the coaxial gap of the air intake pipe, using the air measurement port on the vent adaptor.
  2. Pass if CO2 is no higher than 0.2% or O2 is no lower than 20.6%.
  3. If CO2 is higher or O2 is lower, check the venting system thoroughly.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 67. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.