Viessmann Boiler: Showing Viessmann fault codes in hex on the BMS
Showing Viessmann fault codes in hex on the BMS on a Viessmann boiler: The gateway sends fault codes as decimal numbers. To read them as the hex codes shown on the boiler, mask the value in hex and map the decimal values to the code text in the BMS.
Applies to: Niagara AX or similar BMS with KitControl objects
How to fix showing viessmann fault codes in hex on the bms: step by step
- Convert the decimal fault value to hex using a Numeric Bit And object with a mask input.
- Build an enum range in a Numeric To Enum object listing every Viessmann code.
- Point a bound label on the webpage at the matching slot values.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 511 & 511D LON Type B manual, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.