Viessmann Boiler: Set up LON communication between control units
Set up LON communication between control units on a Viessmann boiler: Steps to set system type, boiler number and LON participant numbers. The LON communication module must be plugged in first.
Applies to: Multi-boiler systems with LON communication
How to fix set up lon communication between control units: step by step
- Vitotronic 100: set coding 1, address 01 to 2 (multi-boiler system).
- Vitotronic 100: set the boiler number in coding 1, address 07.
- Vitotronic 100: set the LON participant number in coding 1, address 77. Each LON participant number can only be used once.
- Vitocontrol-S: set the number of boilers in coding 1, address 35.
- Vitocontrol-S: set the LON participant number in coding 1, address 77 (factory default 5).
- Allow several minutes for data transfer over the LON system.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitocontrol-S VD2/CT3/CM2
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Vitotronic 100 GC1
Source: Viessmann Vitotronic 100 / Vitocontrol-S installation and service instructions, p. 92. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.