Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Set up a Vitodens 200 / B2HA cascade with the Vitotronic 300-K MW2C

Updated · by Aurora Star Tech Inc.

Set up a Vitodens 200 / B2HA cascade with the Vitotronic 300-K MW2C on a Viessmann boiler: The cascade control must be addressed as LON 9 so the boilers can use LON addresses 1 through 8. KMK communication is possible but gives less information.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 300-K MW2C for Vitodens 200 / B2HA

How to fix set up a vitodens 200 / b2ha cascade with the vitotronic 300-k mw2c: step by step

  1. Set the MW2C LON address 77 to a value of 9.
  2. Set the boilers from LON address 1 through 8 (coding address 77).
  3. Set the gateway configuration nviCasConfig to 1 (cascade at LON address 9).
  4. If the boilers communicate by KMK instead of LON, set nviCommConfig to 1.
  5. Expect less data when KMK is used than when LON is used.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Versatronik 581 LON gateway manual, p. 13-14. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.