Viessmann Boiler: Set up a Vitodens 200 / B2HA cascade with the Vitotronic 300-K MW2C
Set up a Vitodens 200 / B2HA cascade with the Vitotronic 300-K MW2C on a Viessmann boiler: The cascade control must be addressed as LON 9 so the boilers can use LON addresses 1 through 8. KMK communication is possible but gives less information.
Applies to: Vitotronic 300-K MW2C for Vitodens 200 / B2HA
How to fix set up a vitodens 200 / b2ha cascade with the vitotronic 300-k mw2c: step by step
- Set the MW2C LON address 77 to a value of 9.
- Set the boilers from LON address 1 through 8 (coding address 77).
- Set the gateway configuration nviCasConfig to 1 (cascade at LON address 9).
- If the boilers communicate by KMK instead of LON, set nviCommConfig to 1.
- Expect less data when KMK is used than when LON is used.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Versatronik 581 LON gateway manual, p. 13-14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.