Viessmann Boiler: Set the fixed high limit to 212 F (100 C)
Set the fixed high limit to 212 F (100 C) on a Viessmann boiler: Only do this if needed. The setting cannot be reversed, and the adjustable high limit must not be above 167 F (75 C) afterward.
Applies to: Vitotronic 100 KW10B fixed high limit
How to fix set the fixed high limit to 212 f (100 c): step by step
- Turn the indicator screw at the rear of the FHL to the 212 F (100 C) position with a flat-head screwdriver.
- Complete the protocol on page 34 of the manual.
- Confirm the adjustable high limit is not set above 167 F (75 C).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 KW10B installation manual, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.