Viessmann Boiler: Set LON participant number and update LON participant list
Set LON participant number and update LON participant list on a Viessmann boiler: Used when the Vitotronic 300 GW2 is connected in a LON BUS system with Vitotronic 200-H. The LON communication module must be fitted first.
Applies to: Vitotronic 300 GW2 with Vitotronic 200-H and Vitocom 300 on LON
Common causes of set lon participant number and update lon participant list
- The same LON participant number is assigned twice in the LON BUS system.
How to fix set lon participant number and update lon participant list: step by step
- Fit the LON communication module (accessory).
- Set the LON participant number in coding 1, address 77. Factory setting is 77: 1.
- Make sure every participant has a different number.
- Make sure the control unit is coded as fault manager (coding 79: 1) and all participants are connected.
- Press the w and OK buttons together for about 2 seconds.
- Press the D button to start the participant check.
- Wait about 2 minutes for the participant list to update.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 GW2 installation and service instructions, p. 66. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.